Call Us: (973) 256-3000 Plast-O-Matic Valves, Inc.
1384 Pompton Avenue
Cedar Grove, NJ 07009 USA
Email:

Installation Instructions for Series CKS

Self Closing Check Valves

1½", 2" & 3"

IMPORTANT - BEFORE INSTALLING

Series CKS check valves will prevent back flow when properly installed and used within the recommended ranges of pressure, temperature, and chemical compatibility. The ultimate determination of material compatability is previous successful use in the same application.

Caution: Plastic materials will degrade in ultraviolet (UV) light or sunlight.

Caution: Polypropylene and PVDF (Kynar) often look similar. Do not install in your system if you are not sure.

MAXIMUM INLET PRESSURE FOR WATER
BODY MAT'L
COLOR
77° (25°C)
105° (40°C)
at MAX. TEMP.
PVC
DARK

GRAY

150 PSI

10 BAR

100 PSI

7 BAR

40 PSI@40°F

3 BAR@60°F

POLYPRO
TRANSLUCENT

WHITE

100 PSI

5 BAR

70 PSI

5 BAR

25 PSI@180°F

2 BAR@105°F

PVDF

(KYNAR)

TRANSLUCENT

WHITE

(YELLOWISH)

150 PSI

10 BAR

120 PSI

8 BAR

30 PSI@280°F

2 BAR@140°F

INSTALLATION INSTRUCTIONS

The valve must be installed in the proper flow direction as indicated by the flow label. All orientations, horizontal and vertical, are suitable.

Threaded Connections: A suitable thread sealant (ex. PTFE tape) should be applied to male tapered threads to assure a "leak-tight" seal. The assembly need only be made "hand-tight" followed by a quarter (1/4) turn with a strap wrench. Do not over tighten or use pipe wrenches on plastic pipe and components.

Caution: PTFE tape will "string" as pipe threads are joined. Loose "strings" could lay across the seating surface and prevent the check valve from completely closing. To avoid this problem, clean out the old tape, and do not apply tape to the first thread.

Caution: Connections should be made only to plastic fittings; metal pipe should only be installed with an intervening plastic nipple. Metal pipe and straight threaded pipe tend to cut, stretch, and distort the plastic bodies, which could result in cracking or leaking over time.

Non-Threaded Connections: For solvent cementing or heat fusion, follow instructions supplied with the cement or fusion equipment, or contact your distributor.

MAINTENANCE

Plast-O-Matic recommends keeping a spare seal kit available for repairs. Seal life will vary in applications due to cycles, temperatures, pressures, chemicals, and concentration. Based on the application, a periodic inspection and maintenance plan should be established. The seal kit part number is "SK" plus the part number. For example, the seal kit for CKS150V-NC-PV is SKCKS150V-NC-PV.


HELPFUL LINKS:

Please click here to return to the CKS Series Web Page

Please click here to return to the Main Instruction Page
Plast-O-Matic Valves, Inc. 1384 Pompton Avenue Cedar Grove,
NJ 07009 USA Phone: (973) 256-3000 Fax: (973) 256-4745
California Warehouse 4054 Brewster Way Riverside, CA 92501
USA phone: (951) 686-2852 Fax: (951) 686-6328
Email: info@plastomatic.com Legacy home page: please click here